Types:KCMA-XJ21A KCMD-XJ21A
Terminal Arrangement:
Register Address | Code | Name | Manual | Setting range | Ex-Factory |
---|---|---|---|---|---|
The first public parameters | |||||
0 | LocK | Set data lock | LOCK=18, Set data unlock LOCK≠18, Set data lock. |
0~50 | 18 |
1 | OP-B | AUX output Opt. | 0:no output; 1:RS232 or RS485; 2:contact the micro-printer; ‘ 3:transmitter 0~10mA 4:transmitter4~20mA |
0~4 | READ ONLY |
2 | Addr | Address | Communication address can be set from 0 to 255 | 0-255 | 1 |
3 | Baud | Communication speed | 1200; 2400; 4800; 9600; | ____ | 9600 |
The Parameters of Each channels(Channel menu level) | |||||
4 | SU+N(1~4) | Setting value | Set the temperature set value (SV) which is the target value for control | Determined by P-SL P-SH | 100 |
5 | AL+N | Alarm value | Please refer to ALP for the alarm mode suitable. | 0 | |
6 | Sc+N | PV Bias | The value set in the PV bias is added to the actual input value to correct the input value. | ±20.0 | 0.0 |
7 | P+N | Proportional band | Set when PI or PID control is performance. For heating / cooling PID action. When P=0,the meter is ON/OFF control |
1~100 | 100 |
8 | I+N | Integral time | Eliminates offset occurring in proportional control. | 0~3000 | 500 |
9 | D+N | Derivative time | Prevents overshoot and/or undershoot caused by integral action effect.. | 0~2000S | 100S |
10 | Hy+N | Differential gap | When the control is ON/OFF control(P=0) Relay contact may repeat its turning ON and OFF due to input fluctuation if measured value (PV) is near the alarm set value.the differential gap setting can prevent the relay contact from ON or OFF repetition. |
0.1~50.0 | 1.0 |
11 | T+N | PID control cycle. | PID control response time | 2~120 | 20S |
12 | Dp+N |
Decimal point position selection | Set the position of the decimal point for the measured value to be displayed. | 0~3 | 0 |
13 | ALP+N | Alarm type | 0: Alarm function OFF; ‘1’ Process high alarm; ‘2’ Process low alarm; ‘3’ Deviation High alarm ; ‘4’ Deviation low alarm; ‘5’ Deviation high/low alarm; ‘6 Band alarm. |
0~6 | According to the request |
14 | Sn+N | Input type | 0~10mA 4~20mA | ||
15 | dIL+N | Range high | The control is displayed after the Input type and Input range. | ||
16 | dIH+N | Range low | |||
17 | AT+N | Autotuning (AT) with learning function | 1: Autotuning (AT) with learning start 0: Autotuning (AT) with learning stop Turns OFF automatically when the AT with learning function is completed. |
0~1 | 0 |
18 | COOL+N | System function Opt. | ‘0’:reverse control(heating) ‘1’:positive control(cooling) |
0~1 | 0 |