Data whose decimal point's presence and/or position depends on input range.
Example:When Read messured value(PV) is -20.0°c,-20.0 is processed as -200;
When Read PID output value is 20,20 is processed as 20 too,bceause PID output value have no decimal point ;
Universal register address: | ||||
---|---|---|---|---|
ID | NAME | Decimal point | Real Register | Holding Register |
0 | Messured value(PV): | yes | 1001H | 44098 |
1 | Manipulated output value (MV): | no | 1101H | 44354 |
2 | Alarm output:4 channels | no | 1200H | 44609 |
KCM-XJ4W(Thermocouple/RTD Universal input Multi-Loop Temperature Controller) | ||||
---|---|---|---|---|
ID | NAME | Decimal point | Real Register | Holding Register |
Communal parameters | ||||
0 | Set data lock | 0 | 0000H | 40001 |
1 | Input type | 0 | 0001H | 40002 |
2 | Alarm output Opt. | 0 | 0002H | 40003 |
3 | PID control cycle. | 0 | 0003H | 40004 |
4 | Decimal position | 0 | 0004H | 40005 |
5 | Range high | 1 | 0005H | 40006 |
6 | Range low | 1 | 0006H | 40007 |
Channel 1 | ||||
10 | Setting Value | 1 | 000AH | 40011 |
11 | Alarm Value | 1 | 000BH | 40012 |
12 | PV Bias | 1 | 000CH | 40013 |
13 | Proportional band | 1 | 000DH | 40014 |
14 | Integral time | 0 | 000EH | 40015 |
15 | Derivative time | 0 | 000FH | 40016 |
16 | Differential gap | 1 | 0010H | 40017 |
17 | Auto tuning | 0 | 0011H | 40018 |
18 | System function Opt. | 0 | 0012H | 40019 |
Channel 2 | ||||
19 | Setting Value | 1 | 0013H | 40020 |
20 | Alarm Value | 1 | 0014H | 40021 |
21 | PV Bias | 1 | 0015H | 40022 |
22 | Proportional band | 1 | 0016H | 40023 |
23 | Integral time | 0 | 0017H | 40024 |
24 | Derivative time | 0 | 0018H | 40025 |
25 | Differential gap | 1 | 0019H | 40026 |
26 | Auto tuning | 0 | 001AH | 40027 |
27 | System function Opt. | 0 | 001BH | 40028 |
Channel 3 | ||||
28 | Setting Value | 1 | 001CH | 40029 |
29 | Alarm Value | 1 | 001DH | 40030 |
30 | PV Bias | 1 | 001EH | 40031 |
31 | Proportional band | 1 | 001FH | 40032 |
32 | Integral time | 0 | 0020H | 40033 |
33 | Derivative time | 0 | 0021H | 40034 |
34 | Differential gap | 1 | 0022H | 40035 |
35 | Auto tuning | 0 | 0023H | 40036 |
36 | System function Opt. | 0 | 0024H | 40037 |
Channel 4 | ||||
37 | Setting Value | 1 | 0025H | 40038 |
38 | Alarm Value | 1 | 0026H | 40039 |
39 | PV Bias | 1 | 0027H | 40040 |
40 | Proportional band | 1 | 0028H | 40041 |
41 | Integral time | 0 | 0029H | 40042 |
42 | Derivative time | 0 | 002AH | 40043 |
43 | Differential gap | 1 | 002BH | 40044 |
44 | Auto tuning | 0 | 002CH | 40045 |
45 | System function Opt. | 0 | 002DH | 40046 |
KCM-XJ4A(Analog Current/Voltage input Multi-Loop Controller) | ||||
---|---|---|---|---|
ID | NAME | Decimal point | Real Register | Holding Register |
Communal parameters | ||||
0 | Set data lock | 0 | 0000H | 40001 |
Channel 1 | ||||
4 | Setting value | 1 | 0004H | 40005 |
5 | Alarm value | 1 | 0005H | 40006 |
6 | PV Bias | 1 | 0006H | 40007 |
7 | Proportional band | 1 | 0007H | 40008 |
8 | Integral time | 0 | 0008H | 40009 |
9 | Derivative time | 0 | 0009H | 40010 |
10 | Differential gap | 1 | 000AH | 40011 |
11 | PID control cycle. | 0 | 000BH | 40012 |
12 | Decimal position | 0 | 000CH | 40013 |
13 | Alarm type | 0 | 000DH | 40014 |
14 | Input type | 0 | 000EH | 40015 |
15 | Range low | 1 | 000FH | 40016 |
16 | Range high | 1 | 0010H | 40017 |
17 | Auto tuning | 0 | 0011H | 40018 |
18 | System function Opt. | 0 | 0012H | 40019 |
Channel 2 | ||||
19 | Setting value | 1 | 0013H | 40020 |
20 | Alarm value | 1 | 0014H | 40021 |
21 | PV Bias | 1 | 0015H | 40022 |
22 | Proportional band | 1 | 0016H | 40023 |
23 | Integral time | 0 | 0017H | 40024 |
24 | Derivative time | 0 | 0018H | 40025 |
25 | Differential gap | 1 | 0019H | 40026 |
26 | Control response time | 0 | 001AH | 40027 |
27 | Decimal position | 0 | 001BH | 40028 |
28 | Alarm type | 0 | 001CH | 40029 |
29 | Input type | 0 | 001DH | 40030 |
30 | Range low | 1 | 001EH | 40031 |
31 | Range high | 1 | 001FH | 40032 |
32 | Auto tuning | 0 | 0020H | 40033 |
33 | System function Opt. | 0 | 0021H | 40034 |
Channel 3 | ||||
34 | Setting value | 1 | 0022H | 40035 |
35 | Alarm value | 1 | 0023H | 40036 |
36 | PV Bias | 1 | 0024H | 40037 |
37 | Proportional band | 1 | 0025H | 40038 |
38 | Integral time | 0 | 0026H | 40039 |
39 | Derivative time | 0 | 0027H | 40040 |
40 | Differential gap | 1 | 0028H | 40041 |
41 | Control response time | 0 | 0029H | 40042 |
42 | Decimal position | 0 | 002AH | 40043 |
43 | Alarm type | 0 | 002BH | 40044 |
44 | Input type | 0 | 002CH | 40045 |
45 | Range low | 1 | 002DH | 40046 |
46 | Range high | 1 | 002EH | 40047 |
47 | Auto tuning | 0 | 002FH | 40048 |
48 | System function Opt. | 0 | 0030H | 40049 |
Channel 4 | ||||
49 | Setting value | 1 | 0031H | 40050 |
50 | Alarm value | 1 | 0032H | 40051 |
51 | PV Bias | 1 | 0033H | 40052 |
52 | Proportional band | 1 | 0034H | 40053 |
53 | Integral time | 0 | 0035H | 40054 |
54 | Derivative time | 0 | 0036H | 40055 |
55 | Differential gap | 1 | 0037H | 40056 |
56 | Control response time | 0 | 0038H | 40057 |
57 | Decimal position | 0 | 0039H | 40058 |
58 | Alarm type | 0 | 003AH | 40059 |
59 | Input type | 0 | 003BH | 40060 |
60 | Range low | 1 | 003CH | 40061 |
61 | Range high | 1 | 003DH | 40062 |
62 | Auto tuning | 0 | 003EH | 40063 |
63 | System function Opt. | 0 | 003FH | 40064 |
KCM-XJ4WA(Analog/Temperature Universal input Multi-Loop Controller) | ||||
---|---|---|---|---|
ID | NAME | Decimal point | Real Register | Holding Register |
Communal parameters | ||||
0 | Set data lock | 0 | 0000H | 40001 |
1 | Control response time | 0 | 0001H | 40002 |
Channel 1 | ||||
5 | Input type | 0 | 0005H | 40006 |
6 | Alarm type | 0 | 0006H | 40007 |
7 | Setting value | 1 | 0007H | 40008 |
8 | Alarm value | 1 | 0008H | 40009 |
9 | PV Bias | 1 | 0009H | 40010 |
10 | Proportional band | 1 | 000AH | 40011 |
11 | Integral time | 0 | 000BH | 40012 |
12 | Derivative time | 0 | 000CH | 40013 |
13 | Differential gap | 1 | 000DH | 40014 |
14 | Auto tuning | 0 | 000EH | 40015 |
15 | System function Opt. | 0 | 000FH | 40016 |
16 | Decimal position | 0 | 0010H | 40017 |
17 | Range high | 1 | 0011H | 40018 |
18 | Range low | 1 | 0012H | 40019 |
Channel 2 | ||||
19 | Input type | 0 | 0013H | 40020 |
20 | Alarm type | 0 | 0014H | 40021 |
21 | Setting value | 1 | 0015H | 40022 |
22 | Alarm value | 1 | 0016H | 40023 |
23 | PV Bias | 1 | 0017H | 40024 |
24 | Proportional band | 1 | 0018H | 40025 |
25 | Integral time | 0 | 0019H | 40026 |
26 | Derivative time | 0 | 001AH | 40027 |
27 | Differential gap | 1 | 001BH | 40028 |
28 | Auto tuning | 0 | 001CH | 40029 |
29 | System function Opt. | 0 | 001DH | 40030 |
30 | Decimal position | 0 | 001EH | 40031 |
31 | Range high | 1 | 001FH | 40032 |
32 | Range low | 1 | 0020H | 40033 |
Channel 3 | ||||
33 | Input type | 0 | 0021H | 40034 |
34 | Alarm type | 0 | 0022H | 40035 |
35 | Setting value | 1 | 0023H | 40036 |
36 | Alarm value | 1 | 0024H | 40037 |
37 | PV Bias | 1 | 0025H | 40038 |
38 | Proportional band | 1 | 0026H | 40039 |
39 | Integral time | 0 | 0027H | 40040 |
40 | Derivative time | 0 | 0028H | 40041 |
41 | Differential gap | 1 | 0029H | 40042 |
42 | Auto tuning | 0 | 002AH | 40043 |
43 | System function Opt. | 0 | 002BH | 40044 |
44 | Decimal position | 0 | 002CH | 40045 |
45 | Range high | 1 | 002DH | 40046 |
46 | Range low | 1 | 002EH | 40047 |
Channel 4 | ||||
47 | Input type | 0 | 002FH | 40048 |
48 | Alarm type | 0 | 0030H | 40049 |
49 | Setting value | 1 | 0031H | 40050 |
50 | Alarm value | 1 | 0032H | 40051 |
51 | PV Bias | 1 | 0033H | 40052 |
52 | Proportional band | 1 | 0034H | 40053 |
53 | Integral time | 0 | 0035H | 40054 |
54 | Derivative time | 0 | 0036H | 40055 |
55 | Differential gap | 1 | 0037H | 40056 |
56 | Auto tuning | 0 | 0038H | 40057 |
57 | System function Opt. | 0 | 0039H | 40058 |
58 | Decimal position | 0 | 003AH | 40059 |
59 | Range high | 1 | 003BH | 40060 |
60 | Range low | 1 | 003CH | 40061 |